DI5000 series is a digital indicator with alarm which has easy-to-see 5 digits/11 segments display, with measuring accuracy of ±0.1%, sampling rate about 0.1 seconds and size of 48x96mm. It is equipped with various functions such as multi range input of thermocouples, resistance thermometers, DC voltage/current and alarm outputs.
Number of Measuring points: 1 point
Input signal : Thermocouple B,R,S,N,K,E,J,T,U,L,WRe5-WRe26,
W-WRe26,NiMo-Ni,CR-AuFe,PlatinelII,
PtRh40-PtRh20,Au-Pt
Resistance thermometer Pt100, JPt100, Pt50, Pt-Co
DC voltage ±20mV, ±100mV, ±5V, ±10V
DC current 0 to 20mA
Accuracy ratings: ±0.1% 1 digit of measuring range (refer to P.1 for details)
Reference junction compensation accuracy: ±1.0 C (ambient temperature 23 °C±10 °C)
±2.0 C (other than above range)
Temperature unit: °C, K
Sampling rate: Approx. 0.1 second
Burnout: Higher limit burnout is provided for thermocouple,
resistance thermometer and DC voltage (only for 20mV).
Absolute value higher limit alarm output operates.
Resistance thermometer measurement current: Approx. 1mA
Rated power voltage: 100 to 240V AC, 50/60Hz
Maximum power consumption: 9VA (100V AC), 12VA (240V AC)
External materials: ABS-polycarbonate (front), polycarbonate (case)
Color: Gray
Weight: Approx. 160g (without option), approx. 220g (with option)
Ambient temperature: -10 to 50 °C (when close installation -10 to 40 °C)
Ambient humidity: 20 to 90% RH (no dew condensation)
| STANDARD
CE marking: EMC directive --- EN61326-1 Class A
Low voltage directive --- EN61010-1, EN61010-2-030
Environmental regulation: RoHS directive
Structure: Conform to IEC60529 IP54 (front part only, not applicable when close
installation)
| ALARM OUTPUT
Output points: Mechanical relay 2 points (standard), maximum 4 points (option)
Contact type: A contact (common independent)
Contact capacity: Resistive load: 240V AC 3A, 30 V DC 3A
Inductive load: 240V AC 1.5A, 30 V DC 1.5A
Minimum load: 5V DC 10mA
Contact protection element: Not included
Alarm: Absolute value higher limit alarm, Absolute value lower limit alarm, FAIL alarm
Performance Specification Sheet | Digital Indicator with Alarm | DI5000 Series | Download |