top

icon
img

DI5000 Series Digital Indicator with Alarm

DI5000 series is a digital indicator with alarm which has easy-to-see 5 digits/11 segments display, with measuring accuracy  of ±0.1%, sampling rate about 0.1 seconds and size of 48x96mm. It is equipped with various functions such as multi range input of thermocouples, resistance thermometers, DC voltage/current and alarm outputs.

 

  • Easy-to-see wide view angle 5digits/11 segments display
  • Various input/output function, 29 multi range input
  • High measuring accuracy ±0.1%
  • Abundant types of alarms, max. 4 alarm output
  • Compact designed (48x96x65mm)

 

 

 

Number of Measuring points: 1 point

Input signal :  Thermocouple    B,R,S,N,K,E,J,T,U,L,WRe5-WRe26,

                                                  W-WRe26,NiMo-Ni,CR-AuFe,PlatinelII,

                                                  PtRh40-PtRh20,Au-Pt

                         Resistance thermometer      Pt100, JPt100, Pt50, Pt-Co

                         DC voltage        ±20mV, ±100mV, ±5V, ±10V

                         DC current        0 to 20mA

 

 

Accuracy ratings:  ±0.1% 1 digit of measuring range (refer to P.1 for details)

Reference junction compensation accuracy: ±1.0 C (ambient temperature 23 °C±10 °C)

                                                                       ±2.0 C (other than above range)

 

 

 

 

Temperature unit: °C, K

Sampling rate: Approx. 0.1 second

Burnout:  Higher limit burnout is provided for thermocouple,

                resistance thermometer and DC voltage (only for 20mV).

                Absolute value higher limit alarm output operates.

Resistance thermometer measurement current: Approx. 1mA

Rated power voltage: 100 to 240V AC, 50/60Hz

Maximum power consumption: 9VA (100V AC), 12VA (240V AC)

External materials: ABS-polycarbonate (front), polycarbonate (case)

Color: Gray

Weight: Approx. 160g (without option), approx. 220g (with option)

Ambient temperature:  -10 to 50 °C (when close installation -10 to 40 °C)

Ambient humidity: 20 to 90% RH (no dew condensation)

 

| STANDARD

 

CE marking: EMC directive --- EN61326-1 Class A

                     Low voltage directive --- EN61010-1, EN61010-2-030

 

Environmental regulation: RoHS directive

Structure: Conform to IEC60529 IP54 (front part only, not applicable when close

                 installation)         

 

 

 

 

| ALARM OUTPUT

 

Output points: Mechanical relay 2 points (standard), maximum 4 points (option)

Contact type: A contact (common independent)

Contact capacity: Resistive load: 240V AC 3A, 30 V DC 3A

                             Inductive load: 240V AC 1.5A, 30 V DC 1.5A

                             Minimum load: 5V DC 10mA

 

Contact protection element: Not included

Alarm: Absolute value higher limit alarm, Absolute value lower limit alarm, FAIL alarm

 

 

Performance Specification Sheet Digital Indicator with Alarm DI5000 Series Download
Leave a feedback